North Zone

Equipment only. No planting. The 13-foot north wall is shared with the house’s bar and sunroom. This is the control room — where the ESP32 controller, intake vent, and house door live.

Climate Profile

MetricValueContext
TemperatureBuffered by house. Warm afternoon (93°F+ peak PM).House thermal mass stores heat, releases in afternoon
Overnight~68°F floor without heatersHouse heat leaks through shared wall
HumidityVariableIntake vent introduces outdoor air here
LightLowest natural light (north-facing)Behind the peaked roof ridge

The 2 PM Anomaly

On March 25, the north zone hit 93.6°F at 2 PM — hotter than the south zone’s 85.2°F at that hour. The south zone had already peaked and was cooling via exhaust fans. The north zone, buffered by the house’s thermal mass and far from the fans, retained its heat longer. This means average temperature overstates the stress in growing zones and understates it in the equipment zone.

Physical Layout

FeatureDetails
House doorInterior door to bar/sunroom. Always closed. Passive thermal bridge.
Intake vent24”×24” (4 sq ft opening). Mechanical actuator with screen. pcf_out_2 pin 5.
ESP32 controllerKincony KC868-E16P board. 192.168.10.111.
Relay panelsPCF8574 I/O expanders → SSR-25DA solid-state relays
CameraAmcrest IP8M-T2599EW-AI-V3, 4K turret, PoE

Airflow Role

The north wall is the air intake side of the greenhouse’s airflow path:

North (intake vent + house door) 
  → Center (fog machine) 
    → South (exhaust fans)

When the economiser gate determines outdoor enthalpy is lower than indoor (cooler and/or drier outside), the vent opens to pull in free cooling. When the vent is closed, the house door still allows passive heat exchange through the shared wall.

Sensor Coverage

SensorAddressIntervalAccuracy
TemperatureModbus addr 2 (Tzone SHT3X)10s±0.3°C
Relative HumiditySame probe10s±2% RH
VPDDerived on ESP3210sCalculated
CO₂Kincony wired analog, 0-5V, 0-10K ppm10sGPIO-based
Light (lux)Kincony LDR, GPIO3510s⚠️ Saturates at ~28K lux

Note: The CO₂ sensor and lux sensor are positioned in/near the north zone, reading greenhouse-average rather than zone-specific values.

Thermal Buffer Value

The house connection is the greenhouse’s most valuable passive climate control feature:

ScenarioEffect
Cold winter night (20°F outdoor)House leaks heat → greenhouse stays ~68°F floor without heaters on moderate nights
Moderate spring night (45°F)No heaters needed at all — house heat maintains setpoint
Hot summer day (95°F)Minimal effect — house AC doesn’t reach greenhouse meaningfully

The north wall acts as a thermal flywheel, damping temperature swings. Combined with the concrete slab’s heat storage, this gives the greenhouse surprisingly good overnight thermal retention.

→ See Heating Systems for the staged heating strategy. → See Cooling & Ventilation for the intake vent and economiser. → See All Zones